Float Charging are designed to supply constant DC source for continuous load and intermittent DC loads and simultaneously keep the connected batteries in fully charged condition.
GENERAL TECHNICAL PARTICULARS |
||||
Sl.No |
Particulars |
Unit |
DUAL FLOAT CUM BOOST CHARGER |
|
A |
General |
|
|
|
1 |
Make |
|
POWERSOFT |
|
2 |
Model |
|
DUAL FLOAT CUM BOOST CHARGER |
|
3 |
Type |
|
SCR FULL CONTROLLED |
|
B |
Rating |
|
|
|
1 |
A.C. Input |
|
|
|
a) |
Voltage & Variation |
V |
415V AC ±10% |
|
b) |
Frequency & Variation |
HZ |
50HZ |
|
c) |
Phase, Wire |
|
Three Phase , Four wire |
|
2 |
D.C. Output |
|
|
|
a) |
Float Voltage ( Adjustable ) |
Volt |
121V DC |
|
b) |
Boost Voltage ( Adjustable ) |
Volt |
124V DC |
|
c) |
Current ( Adjustable ) |
Amp |
120A DC |
|
C |
Performance |
|
|
|
1 |
D.C.Voltage Regulation from No load to Full Load @ nominal AC input voltage at feed back output |
% |
±1% |
|
2 |
Ripple content in D.C. output |
|
Less than 2% |
|
3 |
Guaranteed efficiency at Rated load |
|
≥ 80% |
|
D |
Special features |
|
|
|
a) |
Automatic voltage regulation |
|
Yes |
|
b) |
Current limiting circuitry for both (Load & battery) |
|
Yes |
|
c) |
Smoothing filter circuit |
|
Yes |
|
d) |
Soft‑start feature |
|
Yes |
|
e) |
Automatic & manual operation for Float /Boost selection |
|
Yes |
|
a) |
Surge protection for Rectifier |
|
Yes |
|
3 |
Type of Cooling |
|
AIR NATURAL |
|
e) |
Protection & Controls |
|
|
|
1 |
For AC Input & DC output |
|
MCCB |
|
2 |
For AC Input, Rectifier, filter & DC output Fuses will be provided |
|
YES |
|
3 |
For Auto Manual and float & Boost selection features is provided |
|
YES |
|
F |
Meters |
|
|
|
1 |
Size & Scale |
|
ANALOG - 96x96 mm/ 90deg scale |
|
2 |
Accuracy |
|
class 1.0 |
|
3 |
Provided Meters |
|
|
|
|
a) I/P AC voltmeter with selector switch will be provided to measure the Phase-Phase Voltage |
|||
|
b) O/P DC voltmeter with selector switch will be provided to measure the Charger Voltage, Load Voltage & battery Voltage |
|||
|
c) Battery Ammeter will be provided to measure the Charging & Discharging Current |
|||
|
d) O/P DC ammeter will be provided to measure the Charger load Current |
|||
G |
Enclosure |
|
|
|
1 |
Enclosure Model |
|
INDOOR- DOUBLE DOOR TYPE |
|
2 |
Enclosure construction |
|
|
Freestanding, Floor mounted, Sheet steel construction, Cable entry at BOTTOM |
3 |
Enclosure Degree of protection |
|
IP42 |
|
4 |
Sheet steel thickness (for load bearing and non load bearing) |
mm |
2 MM THICKNESS |
|
5 |
Gland Plate- DETACHABLE TYPE |
Yes |
3MM Thickness |
|
7 |
Approx. Weight (APPROX) |
Kg |
350kg approx |
|
8 |
Ambient temperature |
|
0-50˚C |
|
9 |
Paint Shade (Interior & Exterior) |
|
RAL7032 |
|
10 |
Ground bus furnished with two ground terminals |
Yes |
25*6mm copper bar will be provided |
|
I |
Alarm‑ FACIA |
|
|
|
1 |
DC Negative Earth Fault |
|
|
|
2 |
DC Positive Earth Fault |
|
|
|
3 |
D.C. under Voltage |
|
LED indication will provided in annuciation facia with Reset Push button |
|
4 |
D.C. Over Voltage |
|
||
5 |
Charger overload /Load limiter operated |
|
||
6 |
A.C. over Voltage |
|
||
7 |
A.C.under Voltage/AC Supply fail |
|
||
8 |
AC input fuse fail |
|
||
9 |
Rectifier fuse failure |
|
||
10 |
Filter /Battery fuse fail |
|
LED indication will provided in annuciation facia with Reset Push button |
|
11 |
DC output fuse fail |
|
||
12 |
Charegr fail |
|
||
13 |
Mains fail / Phase fail |
|
||
14 |
Input supply ON (R-phase,Y-phase,B-phase) |
|
Pilot lamp of 22.5mm LED indication will be provided |
|
15 |
Auto/Manual |
|
||
16 |
Float/Boost |
|
||
17 |
DC ON |
|
||
J |
Lamp/Space Heater/Receptacles |
|
|
|
1 |
Internal lamp with door‑switch |
Yes/No |
Yes |
|
2 |
Thermostat & Space heater with On/Off Toggle Switch |
Yes/No |
Yes |
|
3 |
5A 3‑pin universal receptacle |
Yes/No |
Yes |
|
K |
Wiring/Cabling |
|
|
|
1 |
Insulation |
|
PVC insulated |
|
2 |
Voltage grade |
|
1100V of copper conductor |
|
3 |
Minimum conductor size |
|
Power Wire >2.5Sqmm as per current requirement |
|
L |
Name Plate requirements |
Yes/No |
Aluminium(BLACK BACK GROUND WHITE ENGRAVED) |
|
M |
Mandatory Spares |
|
|
|
1 |
Fuses & Fuse links - 100% of total quantity for each Type & rating of fuses used in the system |
|
20% fuse Links will be provided |
Developed and Designed byAcculer Media Technologies